Northern Cables Inc. - Manufacturer of Armored Cables
Français

3C #10 AWG 600V TECK90
Northern Cables Inc.'s TECK90 is an interlocked armored cable for use in petro-chemical, pulp and paper, and other industrial application environments. TECK90 can be used in open and concealed wiring, direct burial, and in hazardous locations.

The insulated conductors are made with cross-linked polyethylene and twisted with an uninsulated ground wire. The twisted core is covered with a PVC jacket, then covered with either interlocked aluminum or galvanized steel, and covered with a PVC jacket over the armour.

TECK90 is manufactured to CSA C22.2#131 and CSA C22.2 #174 to allow it to meet the certain CSA tests including; flame test FT4,-40C cold temperature impact test, low acid gas and sunlight resistance.

TECK90 is available in 600 and 1000-volt constructions from #14 to #2 AWG. Cables can be manufactured up to 30 conductors. Custom cables are available upon request including composites, vertical riser, and colored jackets.

(Download to view PDF's)


600 V TECK90
1000 V TECK90
Blasting Cable


* Download or Print the PDF


2C #12 AWG 600V AC90
AC90 is a flexible interlocked aluminum armored cable approved for use in open and concealed wiring in dry locations.

All AC90 is CSA approved and manufactured with two, three, or four copper conductors insulated with RW90 cross-linked polyethylene rated at 600 volts from #14 to #2 AWG. The bonding conductor is bare copper.

AC90 is a cost effective alternative to conduit wiring. AC90 eliminates the need for conduit, fittings and the labour associated with pulling in wire, threading, and forming conduit. Multiconductor and special construction AC90 can be manufactured. Please make requests to Northern Cables Inc. for Engineering design prod@northerncables.com


* Download or Print the PDF


10C #12 AWG MC Cable
MC-THHN is a UL listed flexible interlocked armored cable for use in branch, feeder, and service circuits in commercial, industrial, multi-residential buildings and places of assembly.

MC-THHN has two or more THHN conductors and can be constructed with solid or stranded copper. The grounding conductor is a green THHN conductor, however, multiple grounding conductors are available.

MC-THHN is available in special constructions including oversized neutral conductors and multi-conductors up to 25 wires. Standard and special constructions can be made from #14 - #1 AWG and is rated for 600 volts. Please make special requests to Northern Cables Inc. for Engineering design prod@northerncables.com
MC & HVC
Super Neutrals






* Download or Print the PDF


BX & Health Care Facility
ACTHH is a UL listed flexible interlocked armored cable for use in branch circuits and feeders in both exposed and concealed areas where allowed by the electric code.

ACTHH has 2, 3, or 4 THHN conductors and can be constructed of either solid or stranded conductors. Each insulated conductor is individually wrapped with paper.

An insulated green ground may or may not be included. All ACTHH cables shall have an internal aluminum bonding wire in intimate contact with the armour.

Standard constructions can be manufactured in sizes #14 AWG to #1 AWG with either steel or aluminum armour. Please make special requests to Northern Cables Inc. for Engineering design prod@northerncables.com
BX & Health Care Facility
* Download or Print the PDF

 


 

SERVICES

 

    INSULATION


  • #14 to #2 AWG
  • XLPE - Cross Linked Polyethylene
  • PVC - Polyvinyl Choride, all colors and striping
  • Nylon
    TWISTING/CABLING

  • #14 to #2 AWG
  • #14 to #1 AWG (MC-THHN only)
  • Composite cables
  • Up to a maximum of 30 Conductors
    ARMORING

  • Interlocking type
  • Aluminum
  • Steel
  • Other metals available on request
  • 0.020" to 0.040" in thickness
  • 0.375" to 0.750" in width
  • Up to 4.0"
JACKETING

  • PVC - Polyvinyl Chloride
  • Other Thermoplastics
  • Up to 2.20" diameter under jacket
  • All colors
  • Custom Printing


CUSTOM ARMOR/JACKETS

Northern Cables Inc. provides custom interlocked armor services on other manufactured cores supplied by the customer. The most common materials for armor are aluminum or galvanized steel. Choice of material thickness and grade can vary depending on the physical properties required by the end user. Other materials are available upon request. In addition Northern Cables can provide custom jacketing services on supplied cores including armored cables. These jackets are available in a range of colors with custom printing. Length Marking in meters and feet is also available. PVC jackets are resistant to water and sunlight, meet FT4, have low acid gas, are rated to minus 40C, and are available in a variety of colors. Other thermoplastics are available on request.


Electrical Test Every cable is subjected to the appropriate CSA and UL electrical tests prior to shipping. These extensive Electrical Tests include: dielectric withstand, conductor resistance, insulation resistance, and continuity.

Mechanical and physical property tests are also performed on a regular basis. These tests include: crush and impact, armour tension, bending radius, cold impact, armour tightness, tensile and elongation of insulation and jackets, as well as aging of polymeric individuals.

TECK90 - CSA C22.2#131 and CSA C22.2 #174
MCTHHN - UL1569
ACTHH - UL4
THHN - UL75


Back to top
View daily copper prices Home  Company Profile  Products/Services  Inventory  Recent Articles  Quotations  Contact Us  Login